
A raging California fire consumed every wood-framed
home in the vicinity. The concrete stucco home is
the only one still standing.
Fire Safety Construction Study
Fire and Acoustic Calculator

FIREWALLS
SECTION 705
705.1 General. Each portion of a building separated by one or more fire walls that comply with the provisions of this section shall be considered a separate building. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates groups that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply. Fire walls located on property lines shall also comply with Section 503.2. Such fire walls (party walls) shall be constructed without openings.
705.2 Structural Stability. Fire walls shall have sufficient structural stability under fire conditions to allow collapse of construction on either side without collapse of the wall for the duration of time indicated by the required fire-resistance rating.
705.3 Materials. Fire walls shall be of any approved noncombustible materials. The fire resistance of concrete or masonry firewalls shall be calculated in accordance with Section 720 or determined by test in accordance with ASTM E-119. All other firewalls shall be tested in accordance with ASTM E-119. Firewalls tested in accordance with ASTM E-119 shall be conducted using the alternative hose stream test procedure described in Section 11.3 of ASTM E-119.
Exception: Deleted
Back
North Carolina:
TABLE 705.4 FIRE WALL FIRE-RESISTANCE RATINGS
|
TABLE 705.4 FIRE
WALL FIRE-RESISTANCE RATINGS |
|
GROUP |
FIRE-RESISTANCE
RATING (hours) |
|
A, B,
E, H-4, I, R-1, R-2, U |
3a |
|
F-1,
H-3b, H-5, M, S-1 |
3 |
|
H-1,
H-2 |
4b |
|
F-2,
S-2, R-3, R-4 |
2 |
|
a. Walls
shall be not less than 2-hour fire-resistance rated where
separating buildings of Type II or V construction.
b. For Group
H-1, H-2 or H-3 buildings, also see Sections 415.4 and 415.5. |
a. Walls shall be not less than 2-hour fire-resistance rated where separating buildings of Type II or V construction.
b. For Group H-1, H-2 or H-3 buildings, also see Sections 415.4 and 415.5.
Back
South Carolina:
VIEW ALL SC APPROVED CODE AMENDMENTS
TABLE 705.4 FIRE WALL FIRE-RESISTANCE RATINGS
|
TABLE 705.4 FIRE
WALL FIRE-RESISTANCE RATINGS |
|
GROUP |
FIRE-RESISTANCE
RATING (hours) |
|
A, B,
E, H-4, I,R-1, R-2,U |
3 |
|
F-1,
H-3b, H-5, M, S-1 |
3 |
|
H-1,
H-2 |
4b |
|
F-2,
S-2, R-3, R-4 |
2 |
|
b. For Group
H-1, H-2 or H-3 buildings, also see Sections 415.4 and 415.5. |
b. For Group H-1, H-2 or H-3 buildings, also see Sections 415.4 and 415.5.
Back
Calculated Fire Resistance of Concrete Masonry Units (CMU)
720.1 General.
The provisions of this section contain procedures by which the fire resistance of specific materials or combinations of materials is established by calculations. These procedures apply only to the information contained in this section and shall not be otherwise used. The calculated fire resistance of concrete, concrete masonry, and clay masonry assemblies shall be permitted in accordance with ACI 216.1/TMS 0216
720.3 Concrete masonry.
The provisions of this section contain procedures by which the fire-resistance ratings of concrete masonry are established by calculations.
720.3.1 Equivalent thickness.
The equivalent thickness of concrete masonry construction shall be determined in accordance with the provisions of this section.
720.3.1.1 Concrete masonry unit plus finishes.
The equivalent thickness of concrete masonry assemblies, T ea, shall be computed as the sum of the equivalent thickness of the concrete masonry unit, Te, as determined by Section 720.3.1.2, 720.3.1.3, or 720.3.1.4, plus the equivalent thickness of finishes, Tef, determined in accordance with Section 720.3.1:
Tea = Te + Tef
Te = Vn/LH = Equivalent thickness of concrete masonry unit (inch) (mm).
where:
V = Net volume of masonry unit (inch³) (mm³).
L = Specified length of masonry unit (inch) (mm).
H = Specified height of masonry unit (inch) (mm)
720.3.1.2 Ungrouted or partially grouted construction.
Te shall be the value obtained for the concrete masonry unit determined in accordance with ASTM C 140.
720.3.1.3 Solid grouted construction.
The equivalent thickness, Te, of solid grouted concrete masonry units is the actual thickness of the unit.
720.3.1.4 Airspaces and cells filled with loose-fill material.
The equivalent thickness of completely filled hollow concrete masonry is the actual thickness of the unit when loose-fill materials are: sand, pea gravel, crushed stone, or slag that meet ASTM C 33 requirements; pumice, scoria, expanded shale, expanded clay, expanded slate, expanded slag, expanded fly ash, or cinders that comply with ASTM C 331; or perlite or vermiculite meeting the requirements of ASTM C 549 and C516, respectively.
Calculating The Equivalent Thickness
Note: For Procedures on Calculating the Equivalent Thickness see NCMA TEK 7-1A
If the hollow unit is 50% core voids Its equivalent solid thickness is 4"
The core area is 40-50% gross area. Equivalent thickness is the solid thickness that would be obtained if the same amount of concrete contained in a hollow unit were re-cast without core holes.
Approximate Volume in Standard Concrete Masonry Units
| Size |
Cores |
Cu ft.
to fill Cores |
% Solid
Volume |
Equivalent
Thickness Inches |
| 4x8x16 |
3 |
.06 |
73.6 |
2.66 |
| 4x8x16 |
2 |
.06 |
73.6 |
2.66 |
| 6x8x16 |
3 |
.15 |
57 |
3.21 |
| 6x8x16 |
2 |
.16 |
54 |
3.06 |
| 8x8x16 |
3 |
.22 |
53.83 |
4.10 |
| 8x8x16 |
2 |
.25 |
51.16 |
3.95 |
| 10x8x16 |
2 |
.34 |
49.27 |
4.70 |
| 12x8x16 |
3 |
.34 |
49.4 |
6.19 |
| 12x8x16 |
2 |
.40 |
44.54 |
5.62 |
* These Units may vary with each manufacturer depending on the style of the block, mold configuration, and wear etc.
Back
Table 720.3.2
International Building Code Fire Resistance-Rated Construction
Minimum Equivalent Thickness (inches) of Bearing or Nonbearing Concrete Masonry Walls
Fire Resistance Rating (hours)
| |
Fire Resistance
Rating (hours) |
| Type of
Aggregate |
1/2 |
3/4 |
1 |
1
1/4 |
1
1/2 |
1
3/4 |
2 |
2
1/4 |
2
1/2 |
2
3/4 |
3 |
3
1/4 |
3
1/2 |
3
3/4 |
4 |
| Pumice
of expanded slag |
1.5 |
1.9 |
2.1 |
2.5 |
2.7 |
3.0 |
3.2 |
3.4 |
3.6 |
3.8 |
4.0 |
4.2 |
4.4 |
4.5 |
4.7 |
|
Expanded shale, clay or slate |
1.8 |
2.2 |
2.6 |
2.9 |
3.3 |
3.4 |
3.6 |
3.8 |
4.0 |
4.2 |
4.4 |
4.6 |
4.8 |
4.9 |
5.1 |
|
Limestone, cinders or unexpanded slag |
1.9 |
2.3 |
2.7 |
3.1 |
3.4 |
3.7 |
4.0 |
4.3 |
4.5 |
4.8 |
5.0 |
5.2 |
5.5 |
5.7 |
5.9 |
|
Calcarous of
siliccous gravel |
2.0 |
2.4 |
2.8 |
3.2 |
3.6 |
3.9 |
4.2 |
4.5 |
4.8 |
5.0 |
5.3 |
5.5 |
5.8 |
6.0 |
6.2 |
For S1: 1" = 25.4mm
a. Values between those shown in the table can be determined by
direct interpolation
b. Where combustible members are framed into the wall, the
thickness of solid material between the
end of each member and the opposite face of the wall or
between members set in from opposite
sides, shall not be less than 93 percent of the thickness
shown in the table.
c. Requirements of ASTM C55, C73 or C90 shall apply.
d. Minimum required equivalent thickness corresponding to the
hourly fire-resistance rating for units
a combination of aggregate shall be determined by linear
interpolation based on the percent by
volume of each aggregate used in manufacture. |
For S1: 1" = 25.4mm
a. Values between those shown in the table can be determined by direct interpolation
b. Where combustible members are framed into the wall, the thickness of solid material between the end of each member and the opposite face of the wall or between members set in from opposite sides, shall not be less than 93 percent of the thickness shown in the table.
c. Requirements of ASTM C55, C73 or C90 shall apply.
d. Minimum required equivalent thickness corresponding to the hourly fire-resistance rating for units a combination of aggregate shall be
determined by linear interpolation based on the percent by volume of each aggregate used in manufacture.
Back
|